FEATURES
-
Flush mounted sensor
-
CO2 sensor measurement of indoor air quality (IAQ)
-
Easy and fast installation
-
Capacitive button for air quality indication
-
0 - 10V output
​
The flush mounted sensor module gives you the
flexibility to make different solutions for your ventilation systems. It is now easy to make a demand controlled ventilation (DCV) system by using CO2 sensors. And as it is flush mounted, it will fit existing switching design instead of a different design sensor on the wall.
APPLICATION
The VMI-02VCW01 is a user control and CO2 sensor for ventilation systems in homes and buildings. The device communicates information about the CO2 level via 0-10V signal.
​
The VMI-02VCW01 translates the measured CO2 value
in a range from 400 ppm to 2000 ppm to an output
voltage between 2-10V, where 2V indicates 400 ppm and 10V indicates 2000 ppm.
The sensor module is a device to measure air quality in a residential or commercial environment. The typical application is to measure indoor air quality (IAQ) and transpond to a ventilation unit directly or to a Building Management System. The ventilation unit or Building Management System can use this information for
displaying or controlling the installation to the defined setpoint.
​
The device can be mounted in the most flush
mounted wall boxes in Europe. (For UK and Italy you need an adapter).
VMI-02VCW01
SENSOR MODULE
SENSORS FOR DCV SYSTEMS
OTHER PLATFORM PRODUCTS
FOR RESIDENTIAL VENTILATION
Heat recovery controller PCB - VMD
To integrate in a Heat recovery unit. It supports many different configurations and can be connected to other products either wirelessly or wired.
Mechanical extraction controller PCB - VMC
To integrate in a single fan system for control of the fan wired or wireless.
Digital input/output module - VMS
To connect wired applications to the wireless world
RS485 to RF interface - BRDG
Connect your RS485 product/building control system to the wireless world. Support of many RF products for heating and ventilation.
Ethernet to RF interface - BRDG
Connect the wireless ventilation and heating world to the outside world for new business applications.
Sensors platform - VMS, VMI
On wall or flush mounted CO2, humidity and temperature sensor for your system.
User interface without display (possible flush mount) - VMN
Simple high quality and flexible solution
User interface with display (possible flush mount) - VMI
A user interface to control and adapt the heat recovery PCB
App and cloud solution
Open up new business opportunities